Brands |
N/A Envirco® |
Optional Duct Inlet Connection Size |
N/A 10 in12 in14 in254 mm305 mm356 mm |
Voltage |
N/A 220 V |
Frequency |
N/A 50 Hz60 Hz |
Phase |
N/A 1 |
Full Load Current |
N/A 0.98 A |
Filter Housing Material |
N/A Mill Finished Aluminum |
Industry Standards / Certifications |
N/A cUL listed (115 V, 208-240 V, 277 V) with standard UL 900 filter, File number E152685 (UL507) |
Filter Type |
N/A High Efficiency Particulate Air (HEPA) |
Filtrand |
N/A Particulate |
High Efficiency Particulate Air (HEPA) Filter Efficiency at 0.3 Micron Size |
N/A 99.99 % |
External Static Operating Pressure |
N/A 1.0 inWg200 Pa |
Orientation |
N/A Horizontal |
Nominal Unit Size |
N/A 2 x 2 ft |
Active Filter Face Area |
N/A 3.5 ft² |
Maximum Air Flowrate1 | N/A 670 ft³/min |
Energy Consumption Rate at Maximum Air Flowrate |
N/A 201 W |
Air Flowrate at 90 Feet per Minute (ft/min) Average Speed |
N/A 315 ft³/min |
Energy Consumption Rate at 90 Feet per Minute (ft/min) Average Speed |
N/A 178 W |
Unit Weight2 | N/A 35 lb |
Note |
N/A
Do not operate 2 x 2 units above 400 SCFM. Damage to the filter and/or particle bleed-through can occur. Performance tested in accordance with the (ANSI/AMCA 210-07), (ANSI/ASHRAE 51-07) test standards for Certified Aerodynamic Performance Rating. 90 fpm values based on active filter face area. BTU = Watts x 3.413. |
Dimension A |
N/A 23.63 in600 mm |
Dimension B |
N/A 23.63 in600 mm |
Dimension C |
N/A 12.50 in318 mm |
N/A
Performance and Innovation |
N/A
|
N/A
|