Print Back
The Camfil Farr SlimLine Series 41 Ducted Ceiling Module is ideal for applications where minimal installation space is available and ultra clean air is a requirement.
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
Unit of Measure
Items SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
D4-23.62-23.62-2-02-00-1D-C2-P
SlimLine 23.62 Inch (in) Actual Length (L) Low-Profile High Efficiency Particulate Air (HEPA) Filter Module
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
D4-23.62-41.62-2-02-00-1D-C2-P
SlimLine 41.62 Inch (in) Actual Length (L) Low-Profile High Efficiency Particulate Air (HEPA) Filter Module
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
D4-23.62-47.62-2-02-00-1D-C2-P
SlimLine 47.62 Inch (in) Actual Length (L) Low-Profile High Efficiency Particulate Air (HEPA) Filter Module
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
D5-23.62-23.62-2-02-00-1D-C2-P
SlimLine 23.62 Inch (in) Actual Length (L) Low-Profile High Efficiency Particulate Air (HEPA) Filter Module
SlimLine Low-Profile High Efficiency Particulate Air (HEPA) Filter Modules
D5-23.62-41.62-2-02-00-1D-C2-P
SlimLine 41.62 Inch (in) Actual Length (L) Low-Profile High Efficiency Particulate Air (HEPA) Filter Module
Description N/A The Camfil Farr SlimLine Series 41 Ducted Ceiling Module is ideal for applications where minimal installation space is available and ultra clean air is a requirement.
Brands N/A SlimLine
Actual Width (W) N/A 23.62 in
Actual Length (L) N/A 23.62 in N/A 41.62 in N/A 47.62 in N/A 23.62 in N/A 41.62 in
Actual Height (H) N/A 4.73 in
Resistance at 100 Feet per Minute (FPM) Average Speed N/A 0.27 inWg N/A 0.27 inWg N/A 0.27 inWg N/A 0.47 inWg N/A 0.47 inWg
Unit Weight N/A 21 lb N/A 31 lb N/A 33 lb N/A 21 lb N/A 31 lb
Shipping Weight N/A 24 lb N/A 35 lb N/A 37 lb N/A 24 lb N/A 35 lb
Collar Size N/A 10 in
Efficiency N/A 95 % N/A 95 % N/A 95 % N/A 99.99 % N/A 99.99 %
Particulate Size N/A 0.3 µm
Filter Type N/A N/A N/A N/A High Efficiency Particulate Air (HEPA) N/A High Efficiency Particulate Air (HEPA)
Maximum Depth N/A 1.61 in41 mm
Industry Standards / Certifications N/A International Organization for Standardization (ISO) 9001:2000 Underwriters Laboratories (UL) Class 1
Options N/A Alternate Screen Material of Construction Exterior Housing Insulation Knife-Edge for Gel Seal Filter Grid
Additional Information N/A
  • Unit shall be ducted high efficiency ceiling module consisting of anodized aluminum frame, a galvanized back plate, 41 mm filter pack, polyurethane encapsulating sealant and dual access ports. Maximum module depth shall not exceed 4.73".
  • Sizes shall be as noted on drawings or other supporting materials.
Construction N/A
  • Filter housing shall be constructed of an anodized aluminum frame mated with a galvanized steel back plate. It shall be designed for installation into a T-Bar ceiling grid system.
  • The media pack shall have a maximum depth of 41 mm (1.61") and shall have an efficiency of (95 at 0.3 micron, 99.99 % at 0.3 micron, 99.9995 % at MPPS).
  • Pleat spacing shall be by continuous glass filament separators to prevent media-to-media contact and promote uniform airflow through the media pack.
  • The media pack shall be completely encapsulated in a polyurethane sealant creating a rigid self-supporting pack. The sealant shall be low out gassing, fire-retardant and self-extinguishing.
  • The module shall include an adjustable airflow diffusion disc that is adjustable from the room side through an access port.
  • A second port, accessible from the room side, shall be provided to allow aerosol test challenge introduction or pressure drop measurement.
  • Housing shall be supplied with a (10", 12") collar that includes an integral continuous raised ridge for duct side connection to air system.
Performance N/A
  • The filter shall be identified on a label indicating minimum efficiency, tested airflow and pressure drop. The unit shall be bar code serialized for individual unit identification.
  • The module shall be listed by Underwriters Laboratories as UL Class 1.
  • Manufacturer shall provide evidence of facility certification to ISO 9001:2000.
Features N/A The Camfil Farr SlimLine offers:
  • High efficiency leak free particulate control. Available efficiencies include 95 % or 99.99 % when evaluated on particles 0.3 micron and 99.9995 % when evaluated on most penetrating particle size (MPPS).
  • A low profile allowing installation in a minimal depth conserving space for manufacturing or other room components. Constructed of light weight extruded aluminum profiles and joined at the corners with Camfil Farr's Klip-Lok™ mechanism the SlimLine installs in any standard 1-1/2" or 2" T-bar grid system. Seismic tabs are included.
  • A 41 mm filter pack, completely encapsulated in Camfil Farr's CamPure™ polyurethane sealant. CamPure™ is thermally/chemically stable to ensure minimal out-gassing and maintains excellent mechanical properties ensuring high-purity air for the most demanding environments over the life of the filter.
  • A media configuration that is optimized through Controlled Media Spacing (CMS™) resulting in a lower pressure drop than other media pleating techniques. Continuous glass filament separators, encapsulated in a stabilizing adhesive, promote uniform airflow while eliminating media to media contact and fiber break-off associated with other media pleating techniques.
  • An adjustable diffusion disc that promotes uniform airflow over the entire filter and allows filter-to-filter air balancing. Room side adjustment is accomplished through a port in the center divider. An additional port is included for pressure drop measurement and/or aerosol challenge introduction.
  • Either a 10" or 12" collar connection. The collar includes an integral continuous raised ridge to assist in securing flexible ducting.
  • An integral white epoxy powder-coated steel grille with 62 % open area to promote proper airflow and protect the filter element.
Note N/A Camfil Farr has a policy of uninterrupted research, development and product improvement. We reserve the right to change designs and specifications without notice.