Brands |
N/A Envirco® |
Voltage |
N/A 115 V |
Frequency |
N/A 50 Hz60 Hz |
Phase |
N/A 1 |
Full Load Current |
N/A 5.20 A |
Filter Housing Material |
N/A Mill Finished Aluminum |
Industry Standards / Certifications |
N/A cUL listed (115 V, 208-240 V, 277 V) with standard UL 900 filter, File number E152685 (UL507) |
Filter Type |
N/A High Efficiency Particulate Air (HEPA) |
Filtrand |
N/A Particulate |
High Efficiency Particulate Air (HEPA) Filter Efficiency at 0.3 Micron Size |
N/A 99.9 % |
External Static Operating Pressure |
N/A 1.0 inWg |
Intended Application |
N/A Cleanrooms |
Orientation |
N/A Horizontal |
Environment |
N/A Chemical Resistant Corrosive Atmosphere |
Airflow |
N/A 90 FPM ± 10 FPM average velocity, 6" from diffuser screen. Uniformity ± 20% of average or better. |
Nominal Unit Size |
N/A 4 x 4 ft |
Active Filter Face Area |
N/A 14.4 ft² |
Maximum Air Flowrate1 | N/A 1950 ft³/min |
Energy Consumption Rate at Maximum Air Flowrate |
N/A 580 W |
Air Flowrate at 90 Feet per Minute (ft/min) Average Speed |
N/A 1300 ft³/min |
Energy Consumption Rate at 90 Feet per Minute (ft/min) Average Speed |
N/A 220 W |
Unit Weight |
N/A 135 lb |
Note |
N/A
Performance tested in accordance with the (ANSI/AMCA 210-07), (ANSI/ASHRAE 51-07) test standards for Certified Aerodynamic Performance Rating. 90 fpm values based on active filter face area. BTU = Watts x 3.413. |
Dimension A |
N/A 47.63 in1210 mm |
Dimension B |
N/A 47.63 in1210 mm |
Dimension C |
N/A 16.67 in424 mm |
N/A
Welded aluminum cabinet with exterior finished in corrosion resistant polyurethane enamel. |
N/A Aluminum framed High Efficiency Particulate Air (HEPA) type, with a minimum efficiency of 99.99 % at 0.3 micron, aerosol challenged (zero probed). |
N/A Direct drive, continuous duty motor with sealed-for-life bearings and inherent overload protection. The blower assembly is electronically (dynamically) balanced and is designed to provide rated airflow through a 50 % increase in initial static pressure. |
N/A Fewer components mean lower installed costs. With use of the MAC 10® LEDC 4 x 4 unit, additional savings are captured in the ceiling plenum because less grid is required and fewer electrical connections are needed. Even better, this model also provides a lower sound level than most competitive 2 x 4 fan filter units. |
N/A
|
N/A
|