Print Back
The Camfil Farr SlimLine Series 41 Ducted Ceiling Module is ideal for applications where minimal installation space is available and ultra clean air is a requirement.
Unit of Measure

Specifications

Brands

N/A SlimLine

Actual Width (W)

N/A 23.62 in

Actual Length (L)

N/A 47.62 in

Actual Height (H)

N/A 4.73 in

Resistance at 100 Feet per Minute (FPM) Average Speed

N/A 0.67 inWg

Unit Weight

N/A 33 lb

Shipping Weight

N/A 37 lb

Collar Size

N/A 12 in

Efficiency

N/A 99.99 %

Particulate Size

N/A Most Penetrating Particle Size (MPPS)

Filter Type

N/A Ultra Low Penetration Air (ULPA)

Maximum Depth

N/A 1.61 in41 mm

Industry Standards / Certifications

N/A International Organization for Standardization (ISO) 9001:2000 Underwriters Laboratories (UL) Class 1

Options

N/A Alternate Screen Material of Construction Exterior Housing Insulation Knife-Edge for Gel Seal Filter Grid

Additional Information

N/A

  • Unit shall be ducted high efficiency ceiling module consisting of anodized aluminum frame, a galvanized back plate, 41 mm filter pack, polyurethane encapsulating sealant and dual access ports. Maximum module depth shall not exceed 4.73".
  • Sizes shall be as noted on drawings or other supporting materials.

Construction

N/A

  • Filter housing shall be constructed of an anodized aluminum frame mated with a galvanized steel back plate. It shall be designed for installation into a T-Bar ceiling grid system.
  • The media pack shall have a maximum depth of 41 mm (1.61") and shall have an efficiency of (95 at 0.3 micron, 99.99 % at 0.3 micron, 99.9995 % at MPPS).
  • Pleat spacing shall be by continuous glass filament separators to prevent media-to-media contact and promote uniform airflow through the media pack.
  • The media pack shall be completely encapsulated in a polyurethane sealant creating a rigid self-supporting pack. The sealant shall be low out gassing, fire-retardant and self-extinguishing.
  • The module shall include an adjustable airflow diffusion disc that is adjustable from the room side through an access port.
  • A second port, accessible from the room side, shall be provided to allow aerosol test challenge introduction or pressure drop measurement.
  • Housing shall be supplied with a (10", 12") collar that includes an integral continuous raised ridge for duct side connection to air system.

Performance

N/A

  • The filter shall be identified on a label indicating minimum efficiency, tested airflow and pressure drop. The unit shall be bar code serialized for individual unit identification.
  • The module shall be listed by Underwriters Laboratories as UL Class 1.
  • Manufacturer shall provide evidence of facility certification to ISO 9001:2000.

Features

N/A The Camfil Farr SlimLine offers:

  • High efficiency leak free particulate control. Available efficiencies include 95 % or 99.99 % when evaluated on particles 0.3 micron and 99.9995 % when evaluated on most penetrating particle size (MPPS).
  • A low profile allowing installation in a minimal depth conserving space for manufacturing or other room components. Constructed of light weight extruded aluminum profiles and joined at the corners with Camfil Farr's Klip-Lok™ mechanism the SlimLine installs in any standard 1-1/2" or 2" T-bar grid system. Seismic tabs are included.
  • A 41 mm filter pack, completely encapsulated in Camfil Farr's CamPure™ polyurethane sealant. CamPure™ is thermally/chemically stable to ensure minimal out-gassing and maintains excellent mechanical properties ensuring high-purity air for the most demanding environments over the life of the filter.
  • A media configuration that is optimized through Controlled Media Spacing (CMS™) resulting in a lower pressure drop than other media pleating techniques. Continuous glass filament separators, encapsulated in a stabilizing adhesive, promote uniform airflow while eliminating media to media contact and fiber break-off associated with other media pleating techniques.
  • An adjustable diffusion disc that promotes uniform airflow over the entire filter and allows filter-to-filter air balancing. Room side adjustment is accomplished through a port in the center divider. An additional port is included for pressure drop measurement and/or aerosol challenge introduction.
  • Either a 10" or 12" collar connection. The collar includes an integral continuous raised ridge to assist in securing flexible ducting.
  • An integral white epoxy powder-coated steel grille with 62 % open area to promote proper airflow and protect the filter element.

Note

N/A Camfil Farr has a policy of uninterrupted research, development and product improvement. We reserve the right to change designs and specifications without notice.