Extra low watts, sound, and profile
The Envirco® LEAC2 fan filter unit is the first (FFU) with low watts, low profile, and high airflow. The MAC 10® LEAC2 2 x 4 ft (600 x 1210 mm) provides one of the lowest power consumption levels of any FFU in the industry. Running at only 208 watts @ 90 fpm, the unit uses less energy than traditional FFUs and reduces operating costs. The MAC 10® LEAC2 standard model maintains a low profile, measuring less than 13" (318 mm) tall. The MAC 10® LEAC2 comes standard with the filter integral with the unit housing. Room-side replaceable filters and motor blower removable from room-side are available.
Unit of Measure

Specifications

Brands

Envirco®

Optional Duct Inlet Connection Size

10 in12 in14 in254 mm305 mm356 mm

Voltage

115 V

Frequency

50 Hz60 Hz

Phase

1

Full Load Current

1.8 A

Filter Housing Material

Mill Finished Aluminum

Industry Standards / Certifications

cUL listed (115 V, 208-240 V, 277 V) with standard UL 900 filter, File number E152685 (UL507)

Filter Type

High Efficiency Particulate Air (HEPA)

Filtrand

Particulate

High Efficiency Particulate Air (HEPA) Filter Efficiency at 0.3 Micron Size

99.99 %

External Static Operating Pressure

1.0 inWg200 Pa

Orientation

Horizontal

Performance

Nominal Unit Size

2 x 3 ft

Active Filter Face Area

3.8 ft²
Maximum Air Flowrate1 687 ft³/min

Energy Consumption Rate at Maximum Air Flowrate

198 W

Air Flowrate at 90 Feet per Minute (ft/min) Average Speed

340 ft³/min

Energy Consumption Rate at 90 Feet per Minute (ft/min) Average Speed

189 W
Unit Weight2 53 lb

Note

Performance tested in accordance with the (ANSI/AMCA 210-07), (ANSI/ASHRAE 51-07) test standards for Certified Aerodynamic Performance Rating.

90 fpm values based on active filter face area. BTU = Watts x 3.413.

Dimensions

Dimension A

23.63 in600 mm

Dimension B

35.63 in905 mm

Dimension C

14.61 in371 mm

Additional Information

N/A Performance and Innovation
The LEAC2 comes standard with a solid-state speed control and will operate against high external static pressure to provide superior filter life. By taking advantage of a unique combination of motor blower technology, along with Envirco®'s proprietary baffling system, the LEAC2 delivers uniform airflow over a wide range of cfm.

Envirco® MAC 10® FFUs are used worldwide for a variety of critical clean air applications. Learn more about how you can benefit from the LEAC2 in your next critical room application.

Features

N/A

  • Low watts, low profile, and low operating costs
  • Solid State Speed Control - 3 speed switch is not available (LEAC 2 x 4 only)
  • Integrated PSC Motorized Backward Inclined Impeller
  • Walkable plenum (excluding pre-filter), rated to 250 lbs.
  • Snap-in 20 x 20 washable pre-filter
  • Manufactured to IEST recommended practices; IESTRP-CC036.1
  • Aluminum Diffuser Screen (RSRE)
  • Room-side Challenge Ports standard on RSRE
  • Room-side Replaceable Filter and Motor Assembly standard on RSRE

Optional Features

N/A

  • Modbus Equipped Variable Speed Control Card (ENAC) compatible with Envirco® control systems
  • Direct connection to air conditioning supply
  • Ducted Inlet Connection (shipped loose)
    • 10" (254 mm)
    • 12" (305 mm)
    • 14" (356 mm)
  • Airflow indicator light: Allows external monitoring of motor operation; green indicator is ON during normal operation
  • Filter Load Indicator Light
  • Pressure Transducer for continuous filter monitoring
  • Flow-through light fixture provides illumination with minimal airflow disruption
  • Powder coat white paint or stainless steel housing
  • Room-side 3/8" Challenge Ports: convenient aerosol challenge and HEPA filter testing
  • ULPA 99.9995 % at 0.12 micron PTFE and low boron
  • 3/4" Knife Edge: Permits easy placement in gel track ceiling grid system (available on RSRE units only)
  • MERV 8 pre-filter available
  • Stainless Steel Diffuser Screen

  • 1 Maximum CFM rating base on free air volumes at high speed motor setting.
  • 2 Add approximately 10 lb for Stainless Steel exterior.