The Envirco® MAC 10® fan filter unit, was the first (FFU) to combine low sound, low watts and a low profile. Measuring only 51 dBA, the MAC 10® Original Standard (2 ft x 4 ft [600 mm x 1,210 mm]) provides one of the lowest sound levels of any FFU in the industry. Running at only 310 watts @ 90 fpm, the unit uses less energy than traditional FFUs, lowering operating costs. The MAC 10® Original maintains a low profile, measuring less than 13" (330 mm).
Specifications
Brands |
N/A Envirco® |
Voltage |
N/A 220 V |
Frequency |
N/A 50 Hz60 Hz |
Phase |
N/A 1 |
Full Load Current |
N/A 1.5 A |
Optional Duct Inlet Connection Size |
N/A 10 in12 in254 mm305 mm |
Additional Description |
N/A Variable Speed Switch |
Industry Standards / Certifications |
N/A UL Listed (115 V, 208-240 V, 277 V) with standard UL900 filter, File number E152685 (UL507) |
Filter Type |
N/A High Efficiency Particulate Air (HEPA) |
Filtrand |
N/A Particulate |
Efficiency |
N/A 99.99 % |
Filter Housing Material |
N/A Mill Finished Aluminum |
Particulate Size |
N/A 0.3 µ |
Orientation |
N/A Horizontal |
Performance
Nominal Unit Size |
N/A 2 x 2 ft |
Active Filter Face Area |
N/A 3.5 ft² |
Maximum Air Flowrate |
N/A 410 ft³/min |
Energy Consumption Rate at Maximum Air Flowrate |
N/A 200 W |
Air Flowrate at 90 Feet per Minute (ft/min) Average Speed |
N/A 315 ft³/min |
Energy Consumption Rate at 90 Feet per Minute (ft/min) Average Speed |
N/A 165 W |
Sound Level at 90 Feet per Minute (ft/min) Average Speed |
N/A 48 dBA |
Unit Weight |
N/A 41 lb |
Dimensions
Dimension A |
N/A 23.63 in600 mm |
Dimension B |
N/A 23.63 in600 mm |
Dimension C |
N/A 12.51 in318 mm |
Additional Information
N/A MAC 10® Original comes standard with the filter integral with the unit housing, requiring the unit to be removed from the ceiling grid to replace the filter. The RSR unit has the filter sealed to the unit using the knife edge/gel seal construction, allowing the filter to be replaced from the room side. The RSRE unit has the added feature of allowing the motor blower and filter to be replaced from the room side. |
Features
N/A
|
Optional Features
N/A
|
Note
N/A
Performance tested in accordance with the (ANSI/AMCA 210-07), (ANSI/ASHRAE 51-07) test standards for Certified Aerodynamic Performance Rating. |