The Camfil Farr SlimLine Series 41 Ducted Ceiling Module is ideal for applications where minimal installation space is available and ultra clean air is a requirement.
Unit of Measure

Specifications

Brands

SlimLine

Actual Width (W)

23.62 in

Actual Length (L)

47.62 in

Actual Height (H)

4.73 in

Resistance at 100 Feet per Minute (FPM) Average Speed

0.67 inWg

Unit Weight

33 lb

Shipping Weight

37 lb

Collar Size

12 in

Efficiency

99.99 %

Particulate Size

Most Penetrating Particle Size (MPPS)

Filter Type

Ultra Low Penetration Air (ULPA)

Maximum Depth

1.61 in41 mm

Industry Standards / Certifications

International Organization for Standardization (ISO) 9001:2000 Underwriters Laboratories (UL) Class 1

Options

Alternate Screen Material of Construction Exterior Housing Insulation Knife-Edge for Gel Seal Filter Grid

Additional Information

N/A

  • Unit shall be ducted high efficiency ceiling module consisting of anodized aluminum frame, a galvanized back plate, 41 mm filter pack, polyurethane encapsulating sealant and dual access ports. Maximum module depth shall not exceed 4.73".
  • Sizes shall be as noted on drawings or other supporting materials.

Construction

N/A

  • Filter housing shall be constructed of an anodized aluminum frame mated with a galvanized steel back plate. It shall be designed for installation into a T-Bar ceiling grid system.
  • The media pack shall have a maximum depth of 41 mm (1.61") and shall have an efficiency of (95 at 0.3 micron, 99.99 % at 0.3 micron, 99.9995 % at MPPS).
  • Pleat spacing shall be by continuous glass filament separators to prevent media-to-media contact and promote uniform airflow through the media pack.
  • The media pack shall be completely encapsulated in a polyurethane sealant creating a rigid self-supporting pack. The sealant shall be low out gassing, fire-retardant and self-extinguishing.
  • The module shall include an adjustable airflow diffusion disc that is adjustable from the room side through an access port.
  • A second port, accessible from the room side, shall be provided to allow aerosol test challenge introduction or pressure drop measurement.
  • Housing shall be supplied with a (10", 12") collar that includes an integral continuous raised ridge for duct side connection to air system.

Performance

N/A

  • The filter shall be identified on a label indicating minimum efficiency, tested airflow and pressure drop. The unit shall be bar code serialized for individual unit identification.
  • The module shall be listed by Underwriters Laboratories as UL Class 1.
  • Manufacturer shall provide evidence of facility certification to ISO 9001:2000.

Features

N/A The Camfil Farr SlimLine offers:

  • High efficiency leak free particulate control. Available efficiencies include 95 % or 99.99 % when evaluated on particles 0.3 micron and 99.9995 % when evaluated on most penetrating particle size (MPPS).
  • A low profile allowing installation in a minimal depth conserving space for manufacturing or other room components. Constructed of light weight extruded aluminum profiles and joined at the corners with Camfil Farr's Klip-Lok™ mechanism the SlimLine installs in any standard 1-1/2" or 2" T-bar grid system. Seismic tabs are included.
  • A 41 mm filter pack, completely encapsulated in Camfil Farr's CamPure™ polyurethane sealant. CamPure™ is thermally/chemically stable to ensure minimal out-gassing and maintains excellent mechanical properties ensuring high-purity air for the most demanding environments over the life of the filter.
  • A media configuration that is optimized through Controlled Media Spacing (CMS™) resulting in a lower pressure drop than other media pleating techniques. Continuous glass filament separators, encapsulated in a stabilizing adhesive, promote uniform airflow while eliminating media to media contact and fiber break-off associated with other media pleating techniques.
  • An adjustable diffusion disc that promotes uniform airflow over the entire filter and allows filter-to-filter air balancing. Room side adjustment is accomplished through a port in the center divider. An additional port is included for pressure drop measurement and/or aerosol challenge introduction.
  • Either a 10" or 12" collar connection. The collar includes an integral continuous raised ridge to assist in securing flexible ducting.
  • An integral white epoxy powder-coated steel grille with 62 % open area to promote proper airflow and protect the filter element.

Note